$500+ Orders on Lesman.com Ship Free via UPS Ground
Smart temperature transmitter, single or dual universal input, 4-20 mA and HART or Honeywell DE protocols, or Foundation Fieldbus. 125 mSec update time, digial accuracy to ±0.10° C (Pt100Ω). Replaces the retired Honeywell STT350 temperature transmitter.
Honeywell SmartLine STT850 temperature transmitters deliver high accuracy and stability across a wide ambient temperature range. Built on the SmartLine modular platform, they include polarity insensitive wiring connections and built-in diagnostics for low total cost of ownership and easy maintenance.
- Single or dual universal input for RTDs, thermocouples, mV, and Ohms
- Digital accuracy up to 0.1°C for RTD
- 125 mSec update time for single inputs, 250 mSec update for dual inputs
- Stability up to ±0.01% upper range limit per year for 10 years
- Advanced graphics LCD display: Up to 8 display screens, two line x 16 character, displays up to six data points, and can rotate 0°, 90°, 180°, or 270° position for optimal visibility
- Integral three-button configuration for zero, span, and other options
- For HART configuration, use handheld HART communicator, Field Device Manager (FDM), or Pactware with a HART modem. For DE configuration, use Honeywell SCT3000 software. For Foundation Fieldbus, use FDM
- Dual input for differential, averaging, redundant, or split range measurement
- Built-in galvanic isolation and sensor break protection
- Comprehensive on-board diagnostics for transmitter and sensors
- 4-20 mA DC analog output, HART 7 and digital output, Honeywell DE, and Foundation Fieldbus models
- Alarms for PV high, PV low, critical diagnostics, redundant input, PV rate of change, PV deviation
- Dual compartment housing
- Full compliance to SIL 2/3 requirements
- FM, CSA, ATEX, IECEx approvals
Model Selection Guide
Use this table to find the right model for your application. Don't see the option you need? Call a Lesman sales specialist at 800-953-7626.
Make one selection from each table section below to build your complete model number. Make note of the Availability column to be sure you're building a valid transmitter. A complete STT850 model number looks like this: STT750- _ - _- _ -_ _ _- _ _ _ - _ - _ _ _ _ - _ _ - 0000
Description | Catalog Number | Availability | |
---|---|---|---|
Temperature Transmitter, Universal Input, Factory Standard Configuration | STT850 | ● | |
Inputs | Single Temperature Input | S- | ● |
Dual Temperature Inputs | T- | e | |
Digital Output | No Digital Output | 0- | ● |
With Digital Output | 1- | a | |
Approvals | None | 0- | ● |
FM Approved | A- | e | |
CSA Approved | B- | ● | |
ATEX Approved | C- | ● | |
IECEx Approved | D- | ● | |
Electronic Housing | Aluminum Housing, 1/2" NPT Connection | A _ _ - | ● |
Aluminum Housing, 1/2" NPT Connection, Lightning Protection | C _ _- | ● | |
316 Stainless Steel Housing, 1/2" NPT Connection | E _ _ - | ● | |
316 Stainless Steel Housing, 1/2" NPT Connection, Lightning Protection | G _ _ - | ● | |
Output | 4-20 mA DC Analog Output, HART Protocol | _ H _ - | ● |
4-20 mA DC Analog Output, Honeywell DE Protocol | _ D _ - | ● | |
Foundation Fieldbus Digital Protocol | _ F _- | ● | |
Interface | No Indicator, No Configuration Buttons | _ _ 0- | ● |
No Indicator, Zero/Span Configuration Buttons | _ _ A- | f | |
Basic Digital Indicator, No Configuration Buttons | _ _B- | ● | |
Basic Digital Indicator, Configuration Button Interface | _ _ C- | ● | |
Advanced Digital Indicator, No Configuration Button Interface | _ _ D- | ● | |
Advanced Digital Indicator, Configuration Button Interface | _ _ E- | ● | |
Diagnostics | Standard Diagnostics | 1 _ _- | ● |
Advanced Diagnostics: Rate of Change and Deviation Alarm | 2 _ _- | c | |
Configuration | No Write Protection, Fail High, Standard High/Low Output Limits | _ 1S- | f |
No Write Protection, Fail Low, Standard High/Low Output Limits | _ 2S- | f | |
Write Protection, Fail High, Standard High/Low Output Limits | _ 3S- | f | |
Write Protection, Fail Low, Standard High/Low Output Limits | _ 4S- | f | |
Write Protection, Fieldbus High/Low Output Limits | _ 5S- | g | |
No Write Protection, Fieldbus High/Low Output Limits | _ 6S- | g | |
Calibration | Factory Standard Single Calibration | A- | ● |
Custom Single Calibration (Unit Data Required) | B- | ● | |
Mounting Bracket | None | 0 _ _ _- | ● |
Carbon Steel Flat Pipe Mounting Bracket | 1 _ _ _- | ● | |
Carbon Steel Angle Pipe Mounting Bracket | 2 _ _ _- | ● | |
Carbon Steel Wall Mounting Bracket | 5 _ _ _- | ● | |
316 SS Flat Pipe Mounting Bracket | 3 _ _ _- | ● | |
316 SS Angle Pipe Mounting Bracket | 4 _ _ _- | ● | |
316 SS Wall Mounting Bracket | 6 _ _ _- | ● | |
Tag | None | _ 0 _ _- | ● |
Wired Stainless Steel Tag (Up to 4 Lines, 26 Char Ea.) | _ 1 _ _- | ● | |
Conduit Plugs and Connectors | None | _ _ A0- | ● |
1/2" NPTM to 3/4" NPTF 316 SS Certified Conduit Adapter | _ _ A2- | ● | |
1/2" NPT 316 SS Certified Conduit Plug | _ _ A6- | ● | |
1/2" NPT Minifast® 4-Pin (Not for Explosion-Proof Use) | _ _ A8- | ● | |
Certifications | None | 00- | ● |
Calibration Test Report, Certificate of Compliance | F1- | ● | |
Certificate of Origin | F5- | ● | |
SIL 2/3 Certification | FE- | j |
Restrictions
a Available only on single input models.
c Not available with Honeywell DE protocol.
e Not available with digital output.
f Not available with Foundation Fieldbus.
g Available only on Foundation Fieldbus models.
j Available only with HART communications and write protection enabled.
HART | Yes |
---|---|
SIL-Rated | Yes |
To build your complete part number, make a selection from each table section below. Your completed model and its price will appear in the Results section. If you don't see the options you need, call us.
Results
Please complete your model selections. |