Honeywell HC900 process automation and safety controller combines analog process control, logic control, sequence control, batch programming, and data management all in a single integrated package combined with SIL safety functions for emergency shutdown and critical control.
Perform loop, logic, and safety control functions from one single flexible system with the latest release of Honeywell's HC900 process and safety system. One configuration software package manages the system, and you won't have to work with Ethernet bridge cards or peripherals to get your controller onto your LAN. With its TUV certification, the ControlEdge HC900 safety system can be used in critical safety control applications requiring SIL2.
The flexible, scalable architecture is the ideal system for meeting the needs of demanding applications, like thermal control in boilers, furances, kilns, and dryers, unit processing in food and beverage, pharmaceutical, pulp and paper, and chemical applications, spill prevention and emergency shutdown safety applications, pipeline monitoring, and more.
- Common set of hardware/software tools for both process and safety applications
- Reduced configuration time with process-specific function blocks: setpoint programming, carbon potential, dewpoint control, sequencer, and I/O validation safety
- PID Control with advanced Accutune III auto-tuning and fuzzy overshoot suppression algorithm
- Flexible and scalable, expandable to 12 racks, more than 4,000 digital IO points, and 15,000 function blocks in a single system
- Supports Honeywell Field Device Manager (FDM) using HART IP, and supports HART function blocks when used with universal IO module — Provides a 50% reduction in HART field device configuration time and maintenance, and a 30% reduction in additional cost for extra hardware, like HART modems
- SIL Universal IO with each channel soft-configurable as AI, AO, DI, DO with line monitoring (TUV certified SIL2)
- Easy integration with HMI, SCADA, OPC-UA or other third-party solutions using open Ethernet connectivity and Modbus TCP protocol
- Heavy duty steel rack, CPU/P-S/I-O cards G3 conformal coated for harsh industrial environments
- Color touchscreen operator interface for controller integrated database and pre-built displays
Model Selection Guide
Use this table to find the right model for your application. Don't see the option you need? Call a Lesman sales specialist at 800-953-7626
Description | Click for Price and Availability | ||||||
---|---|---|---|---|---|---|---|
Non-SIL Controllers |
CPU | Analog IN | Analog OUT | Digital I/O | Function Blocks | Network Ports | |
C30 | 96 Universal 192 High Level |
40, 192 External Power | 384 | 400 | 1 | 900C30-0460 | |
C50 | 1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 2000 | 1 | 900C50-0460 | |
C70 | 1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 15000 | 2 | 900C70-0460 | |
C75 (Redundant) |
1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 15000 | 2 | 900C75-0460 | |
TUV SIL2-Rated Controllers |
C30S | 96 Universal 192 High Level |
40, 192 External Power | 384 | 400 | 1 | 900C30S-0460 |
C50S | 1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 2000 | 1 | 900C50S-0460 | |
C70S | 1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 15000 | 2 | 900C70S-0460 | |
C75S (Redundant) |
1152 Universal 2304 High Level |
480, 2304 External Power | 4608 | 15000 | 2 | 900C75S-0460 | |
I/O Scanners | One-Port for Remote Rack (Non-Redundant CPU) | 900S50-0460 | |||||
Two-Port for Remote Rack (Redundant CPU) | 900S75-0460 | ||||||
SIL-Rated, One-Port for Remote Rack (Non-Redundant CPU) | 900S50S-0460 | ||||||
SIL-Rated, Two-Port for Remote Rack (Redundant CPU) | 900S75S-0460 | ||||||
Redundant Modules | Redundant Switch Module | 900RSM-0200 | |||||
Redundant Power Status Module | 900PSM-0200 | ||||||
Power Supply | 120/240 VAC, 60W | 900P01-0301 | |||||
120/240 VAC, 60W, SIL-Rated | 900P01-0401 | ||||||
24 VDC, 60W | 900P24-0301 | ||||||
24 VDC, 60W, SIL-Rated | 900P24-0401 | ||||||
I/O Board [Channels per Card] |
Universal Analog Inputs (T/C, RTD, mV, V, 0/4-20 mA) [8] | 900A01-0202 | |||||
High Level Analog Inputs (mA or V) [16] (Inteernal 250-Ohm Resistors Included with Module) | 900A16-0103 | ||||||
Analog Outputs [4] | 900B01-0301 | ||||||
Pulse/Frequency/Quadrature Module [4] (Not for SIL2 Systems) | 900K01-0201 | ||||||
Digital Inputs, Contact [16] | 900G01-0202 | ||||||
Digital Inputs, 24 VDC [16] | 900G02-0202 | ||||||
Digital Inputs, 24 VDC [32] | 900G32-0101 | ||||||
Digital Inputs, 120/240 VAC [16] | 900G03-0202 | ||||||
Digital Outputs, Relay [8] | 900H01-0202 | ||||||
Digital Outputs, 24 VDC [16] | 900H02-0202 | ||||||
Digital Outputs, 24 VDC [32] | 900H32-0302 | ||||||
Digital Outputs, 120/240 VAC [8] | 900H03-0202 | ||||||
Universal I/O SIL2 Assembly for ControlEdge 900 Platform (0/4-20 mA, AI/AO, 24 VDC DI/DO [16] | 900U02-0100 | ||||||
Terminal Block (Select Style Matched to Appropriate I/O Board) (Note 3) |
Low Voltage Terminal Block, Barrier Style European Screw Cage Connections, 20 Points, BLack | 900TBK-0200 | |||||
Low Voltage Terminal Block, US Style Screw Terminal Connections, 20 Points | 900TEK-0200 | ||||||
Low Voltage Terminal Block, 36-Channel, European Screw Cage Connections, Black | 900TCK-0200 | ||||||
High Voltage Terminal Block, Barrier Style European Screw Cage Connections, 20 Points, Red | 900TBR-0200 | ||||||
High Voltage Terminal Block, US Style Screw Terminal Connections, 20 Points, Black | 900TER-0200 | ||||||
RTP Cables (Other Lengths Available) |
Eight-Channel Analog Output (8CH AO) Cable, 2.5M/8.2Ft | 900RTC-BA25 | |||||
32/16 Channel LV Cable, 2.5M/8.2Ft | 900RTC-3425 | ||||||
Low Voltage RTP Cable, 2.5M/8.2Ft (Not for SIL Systems) | 900RTC-L225 | ||||||
High Voltage RTP Cable, 2.5M/8.2Ft (Not for SIL Systems) | 900RTC-H225 | ||||||
Software and Manuals (Note 1) |
HC Designer Configuration Software,
Media Delivery on CD HC Designer Configuration Software, Media Delivery on DVD HC Designer Configuration Software, Media Delivery via Web Download |
HC-DSGRSW HC-EMD700 HC-EM700-ESD |
|||||
HC Utilities Software/Documentation CD | HC-URILSW | ||||||
HC Historian Software/Documentation CD | HC-HISTSW | ||||||
Full Documentation Set on CD | 900ME1-0060-00 | ||||||
Full Documentation, Printed | 900ME2-0060-00 | ||||||
Terminal Board Accessories |
I/O Filler Block Terminal Cover (Note 3) | 900TNF-0200 | |||||
2-Pack Shield Terminal Strip | 900TSS-0001 | ||||||
10-Pack Two-Position Terminal Board Jumpers | 900J02-0001 | ||||||
10-Pack Ten-Position Terminal Board Jumpers | 900J10-0001 |
Notes:
(2) One 250-ohm resistor required for each mA input.
(3) Honeywell recommends that all unused I/O slots are covered. Order one cover (900TNF-0001) per unused slot.
HART | Yes |
---|---|
SIL-Rated | Yes |
Cutout Size | Other |