$500+ Orders on Lesman.com Ship Free via UPS Ground
Fireye's Industrial MB Series Multi-Burner Control System controls the start-up sequence and monitors the flames of up to 20 individual gas, oil or combination gas/oil burners connected to a common valve train.
Fireye's MB multi-burner monitoring system controls the start-up sequence and monitors the flame of up to 20 individual gas, oil or combination gas/oil burners connected to a common valve train. Dynamic on-board diagnostics check for faulty relays, proof of valve closure, high and low fire switch interlocks, and shortened air switch. It can specifically identify which burner caused the initial flame failure.
The MB-600S chassis directly powers pilot and main gas valves and ignition transformers. The built in blower output, purge timing and modulation control, let you add independent limits and a controller to create a complete combustion control system for furnace, oven or other multi-burner applications.
- 3 second flame failure response time (±0.5 seconds)
- 5-, 10-, or 15-second selectable pilot trial for ignition with 5-second pilot proving time
- Compatible with UV7 ultravoilet flame scanners
- Selectable purge time increments from 0-225 seconds in 15-second increments up to 0-60 minutes in 4-minute increments
- UL recognized, FM approved
Model Selection Guide
Use this table to find the right model for your application. Don't see the option you need? Call a Lesman sales specialist at 800-953-7626
Description | Click for Price and Availability | |
---|---|---|
Step 1: Select a chassis for your multiburner control system. All are 120 VAC 50/60 Hz, and include motherboard, relay board, logic module, and power module, four auxiliary inputs, purge modulation, and valve leak testing | ||
Chassis | Burner control chassis with no communications Burner control chassis with RS-232 communications Burner control chassis with RS-485 communications |
MB-600S MB-632S MB-685S |
Step 2: Select a flame sensor module | ||
Sensor Module | Plug-in flame sensor module for UV, flame rod or both, for use with expansion boards Plug-in flame sensor module for UV, flame rod or both |
MB-600PF MBPF-100S |
Step 3: For systems with more than four burners, select expansion board modules and cables | ||
Expansion Modules | Expansion board for up to four additional flame sensor modules Expansion board for up to eight additional flame sensor modules 6-inch cable for expansion board 36-inch cable for expansion board |
MB-604E MB-608E 59-506-1 59-506-3 |
Step 4: Select optional remote display and cable | ||
Display | Remote display module with keypad 6-foot remote display cable 10-foot remote display cable |
MB510 59-507-6 59-507-10 |
Step 5: Select a flame scanner for each burner on your system | ||
Scanners and Accessories | 1/2" NPT straight UV scanner 1/2" NPT straight UV scanner with NEMA 4 enclosure 1/2" NPT 90° UV scanner with 6-foot shielded cable 1" NPT self-check scanner (Requires cable 59-504-010.) |
UV7A4 UV7A4W UV7R4 UV7SC |
10-foot cable required with UV7SC scanner Scanner support, max temperature 200° F Magnifying lens assembly (includes insulated coupling) 1/2" NPTF insulated Nylon coupling for UV7 flame scanners when cooling is required |
59-504-010 36-935 46-185 35-319 |