Differential pressure gauge and transmitter for air and non-combustible gases. Ranges from 0.05” to 50” WC. Gauge: 4" dial, 1/8" NPTF process connections. Transmitter: 10 to 35 VDC (2-wire) power, 4-20 mA output, screw terminal block electrical connection, diaphragm in vertical position mounting. Can be panel- or surface-mounted or fit in weatherproof enclosure. CE approved.
Dwyer's 605 Magnehelic® differential pressure indicating transmitter offers visual monitoring and electronic control of very low differential pressure. It's ideal for control applications in building HVAC systems providing local indication during routine maintenance checks or troubleshooting the system.
The Series 605 combines proven Dwyer Magnehelic gauge mechanical design with Dwyer Series 600 transmitter technology. It comes with an easy-to-read 4" dial gage and two-wire 4-20 mA output.
Typical applications include monitoring pressure in ducts, rooms, or total building pressure, filter monitoring, or local indication of clean room pressures while sending output signal to a control room.
- For visual monitoring and electronic control of very low differential pressure in air and non-combustible gases
- Quick response to pressure changes means no delay in signaling and alerting to critical situations
- Long-service life and minimized down-time with durable and rugged housing and high-quality components
- Zero and span adjustments through protected potentiometers on the gauge's front panel
- Transmitter control loop powered by 10-35 VDC
- 1/8" NPTF process connection, screw terminal block electrical connection
- Stainless steel bezel optional
Model Selection Guide
Use this table to find the right model for your application. Don't see the engineering unit or range you need? Call a Lesman sales specialist at 800-953-7626.
Orders placed before 3PM central time for in stock models ship the same day.
Pressure Range | Maximum Pressure | Accuracy | Click for Price
and Availability | |
---|---|---|---|---|
Electrical | Mechanical | |||
0.05" to 0" to 0.2" WC | 10 PSI | ±4% | ±4% | 605-00N |
0.25" to 0" to 0.25" WC | 10 PSI | ±2% | ±3% | 605-11 |
0" to 0.50" WC | 10 PSI | ±2% | ±3% | 605-0 |
0" to 1.0" WC | 10 PSI | ±2% | ±2% | 605-1 |
0" to 2.0" WC | 2 PSI | ±0.5% | ±2% | 605-2 |
0" to 3.0" WC | 2 PSI | ±0.5% | ±2% | 605-3 |
0" to 6.0" WC | 2 PSI | ±0.5% | ±2% | 605-6 |
0" to 10" WC | 2 PSI | ±0.5% | ±2% | 605-10 |
0" to 20" WC | 11 PSI | ±0.5% | ±2% | 605-20 |
0" to 30" WC | 11 PSI | ±0.5% | ±2% | 605-30 |
0" to 50" WC | 11 PSI | ±0.5% | ±2% | 605-50 |
Accessories | 250-Ohm Precision Resistor | A-277 | ||
Flat Aluminum Flush Mount Bracket | A-298 | |||
Flush Surface Mounting Bracket | A-370 | |||
4" 303SS Straight Static Pressure Probe | A-489 | |||
ABS Weatherproof Enclosure | A-320-B1 |
Dial Size | 4 Inch |
---|---|
Process Connection | 1/8" NPTM Center Back |
Liquid Filled | No |
Accuracy | ±0.5% to ±4%, varies by pressure range |
Measuring Range | 0.05" to 50" WC |