Dwyer GSTA transmitter for gas detection supports electrochemical cell sensors for carbon monoxide (user-selectable range from 0-50 to 0-500 ppm) or nitrogen dioxide (0-10 ppm). Switch-selectable normal or reverse outputs: 4-20 mA, 0-5, 1-5, 0-10, and 2-10 VDC. IP64-rated UV-resistant glass-filled polycarbonate enclosure. CE approved.
Commonly used for measuring the gas concentration in underground parking garages and loading docks or mechanical rooms. Typical coverage from 5000 to 7500 square feet.
- Field-replaceable electrochemical cell sensors for carbon monoxide (user-selectable range from 0-50 to 0-500 ppm) or nitrogen dioxide (0-10 ppm)
- Accuracy (at time of calibration): ±2% full scale for CO, ±3% full scale for NO2. Output drift <5% per year in air
- Response time <45 seconds to 90% CO, <25 seconds to 90% NO2
- Power requirements: 10-35 VDC for current output, 15-35 VDC or 15-29 VAC for voltage output
- Calibration using onboard pushbuttons on LCD models, or using optional A-449 remote LCD display
- Duct or wall mount models
- See Dwyer GSTC for models with BACnet or Modbus communications
Gas Detector Use | Fixed |
---|---|
Gas Type | Toxic |
Gas Detector Technology | Electrochemical Cell |
Gas or Flame | Gas |
To build your complete part number, make a selection from each table section below. Your completed model and its price will appear in the Results section. If you don't see the options you need, call us.
Results
Please complete your model selections. |